SA-V-2L

Tested to VDI 6022

X-CUBE_img_55
Cross flow heat recovery unit
SCHOOLAIR-V_img_173236

Water connections

SCHOOLAIR-V_img_173241

Filter change

SCHOOLAIR-B_img_127933

Levelling foot

SA-V-2L
X-CUBE_img_55
SCHOOLAIR-V_img_173236
SCHOOLAIR-V_img_173241
SCHOOLAIR-B_img_127933

X-CUBE SCHOOLAIR-V-2L

Supply and extract air unit for vertical installation on the façade

Ready-to-connect decentralised ventilation unit for comfortable room temperature control and supply and extract ventilation of rooms such as classrooms, meeting rooms and day-care centres
■ Installation possible during normal school operation
■ Acoustically optimised EC fans with low specific fan power, according to DIN EN 16798-3 SFP = 0
■ Switch-over option to secondary air mode
■ Reduction of fine dust and pollen through integrated air filters in accordance with VDI 6022 – filter class ISO ePM1 65% and extract air ISO coarse 75%
■ Tool-free filter replacement
■ Cross flow heat recovery unit
■ Optional year-round heat recovery operation
■ Highly efficient heat exchanger for heating or cooling as a 2-pipe system
■ Heat exchanger connection on the right-hand side, when viewed from the room
■ Condensate drip tray with or without condensate drain connection
■ Motorised shut-off dampers, normally closed

Optional equipment and accessories
■ Control system FSL-CONTROL III, specially designed and modularly constructed for decentralised ventilation systems
■ Wood panelling in various colours, including TROX ventilation grilles for supply and extract air (self-assembly kit)

Allgemeine Informationen

Functional description

Decentralised supply and extract air units ventilate the room and cover the cooling and heating load in accordance with the technical data. An EC centrifugal fan takes in the outdoor air which then flows through the motorised shut-off damper and the outdoor air filter.
The outdoor air then flows through the cross flow heat recovery unit, which can be switched off if it is more energy efficient. If necessary, the air is heated by the heat exchanger before it is discharged to the room as a displacement flow.
The extract air first passes through the extract air filter, then flows through the heat recovery unit, the extract air fan and the motorised shut-off damper before it is discharged to the outside as exhaust air.
If the indoor air quality is sufficient, the FSL-CONTROL III control system switches to energy-efficient secondary air mode by closing the outdoor air dampers. The control system compares the room air quality setpoint value to the actual value measured by the COsensor and switches automatically between outdoor air and secondary air operation.
In case of a power failure, the outdoor air and exhaust air dampers are closed to ensure fire protection, frost protection and to avoid draughts. This is ensured by a capacitor in each actuator.
Near the external wall, the supply air is discharged into the room with a medium velocity between 0.5 and 0.8 m/s. Due to the induction effect, the supply air velocity is rapidly reduced after entering the room. As a result, in cooling mode, the supply air spreads out like displacement flow over the entire floor area. Near heat sources such as people or equipment, a lift current is formed by natural convection, so that the air is exchanged primarily in these areas.

Information technique

  • FUNCTION
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE

Functional description
Decentralised supply and extract air units ventilate the room and cover the cooling and heating loads in accordance with the technical data. An EC centrifugal fan draws in the outdoor air, which flows through the motorised shut-off damper and the outdoor air filter. The outdoor air then passes through the crossflow heat recovery unit, which can be switched off under operating conditions where heat recovery is not required. If required, the air is heated by the heat exchanger before being discharged into the room as a displacement flow. The extract air passes through the extract air filter, before being discharged to the outside as exhaust air, via the cross-flow heat recovery unit, the extract air fan and the motorised shut-off damper. If the indoor air quality is adequate, the FSL-CONTROL III control system switches to energy-efficient secondary air mode by closing the outdoor air dampers. The control system compares the room air quality setpoints to the actual values measured by the CO2 sensor and switches automatically between outdoor air and secondary air operation. In case of a power failure, the outdoor air and exhaust air dampers are closed to ensure fire protection, frost protection, and to avoid draughts. This function is ensured by a capacitor in each actuator. The supply air flows into the room close to the façade at an average velocity of 0.5 – 0.8 m/s. As a result of the induction effect, the air velocity is rapidly reduced shortly after the air enters the room. As a result, in cooling mode the supply air spreads across the entire floor area as displacement flow. At heat sources such as people or equipment, natural convection creates a buoyant airflow, so that air exchange primarily occurs in these areas.

Width

397 mm

Height

2160 mm

Depth

359 mm

Volume flow rate

150, 200, 250 m³/h (boost 320 m³/h)

nominal volume flow rate

250 m³/h

Sound power level

31 – 46 dB(A)

Heat recovery efficiency

52 %

Maximum operating pressure, water side

6 bar

Maximum operating temperature

75 °C

Supply voltage

1~ 230 V AC, ±10 %, 50/60 Hz

Power rating

226 VA

Weight

70 kg

This specification text describes the general characteristics of the product. Texts for variants can be generated with our Easy Product Finder design programme.

Specification text
SA-V
Under sill ventilation units for vertical installation on the façade
TROX SCHOOLAIR-V under sill ventilation unit with supply and extract air function, heat recovery and switchover option to secondary air mode (depending on air quality) as well as heating and/or cooling function, for vertical installation on the façade:
  • Device casing made of galvanised sheet steel
    • Cover and sheet metal connections: Connection via deep-drawn threads and stainless steel cross-head screws
    • All necessary internal air ducts sealed and insulated by lining
    • Internal electrical cable glands sealed
    • Visible surfaces powder-coated (RAL 9005, jet black)
  • Sound and heat-insulating lining on the suction and discharge side:
    • Glass fibre-laminated mineral wool (building material class A, non-combustible according to DIN 4102, T1), abrasion-resistant up to air velocities of 20 m/s, or closed-cell insulation material
  • The device meets the hygiene requirements of VDI 6022
  • Height-adjustable levelling feet, +40 mm, to compensate for structural tolerances
  • Connection to the on-site outdoor air and exhaust air openings in the façade:
    • With circumferential closed-cell sealing tape on the back of the device, 10 mm thick
    • The intake and discharge resistance of the on-site construction should not exceed 20 Pa at nominal volume flow
  • Room-side extract air intake at the top of the unit front
  • Use of 2 energy-saving EC centrifugal fans:
    • Supply and extract air fan classified in category SFP 0 (< 300 W/(m³/s)) in accordance with DIN EN 16798-3:2017-11
  • Suitable for 4 speed levels:
    • Control via the unit-integrated single-room control
    • Volume flow rate correction possible after installation by adjusting the control voltage
  • Technical requirements of EU Regulation 1253/2014 for non-residential ventilation systems:
    • Compliant and documented in accordance with the regulation
  • Motorised shut-off dampers in outdoor and exhaust air areas:
    • Normally closed in inactive state due to capacitor
    • Open-close actuator 230 V AC
    • Control via the unit-integrated single-room control
  • Automatic switchover to energy-efficient secondary air operation:
    • Only in conjunction with air quality sensor
    • Comparison of setpoints with the internal CO2 sensor readings
    • If the indoor air quality is adequate: Automatic changeover from outdoor air mode to secondary air mode
  • Connection point to the on-site electrical system:
    • Cable for on-site connection (not included in TROX scope of supply)
    • Cable (L, N, PE) with wire end ferrules, approx. 1 m exiting the device
    • On-site electrical system: 1~ 230 V AC, 50 Hz, 3 x 1.5 mm2 (3-core)
  • Electrical components in the device:
    • Completely wired with FSL-CONTROL III control system
    • Control components integrated in the device
    • Connection option for bus communication (optional)
    • Connection of room control panel etc. after opening the customer area of the control system
  • Connection point to the on-site Measurement/Control/ Regulation technology: Rail-mounted terminals type Wago 260
    • Master unit:
      • Optional integration into MCE/BACS via RS485 (Modbus/BACnet)
      • Master-slave connection RS485
      • Digital outputs DO
      • Digital inputs DI
      • Room control panel for measuring room temperature
    • Slave unit:
      • Master-slave connection RS485
  • Connection point to the on-site Measurement/Control/ Regulation technology: Network connection RJ45
    • Optional integration into an on-site MCE/BACS via Ethernet (Modbus/BACnet)
    • RJ45 connection socket as service access to the user interface
  • Under-sill cladding, to be provided by the client:
    • Must have perforations: for supply air intake, for extract air and secondary air intake
    • Must not restrict maintenance work or installation and removal of the unit from the front
    • Clear distance between the front edge of the unit to the inner edge of the under-sill cladding: approx. 30 mm
    • Closed-cell sealing tapes for sealing and adapting to the on-site cladding: not included in the TROX supply package
  • Filter change:
    • Quick filter change
    • Tool-free opening of the filter cover thanks to userfriendly quarter-turn fasteners (after opening the onsite cladding)
    • Accessibility must not be restricted by the on-site sill cladding

Materials and surfaces

0
Standard variant
  • Fixing points for installation:
    • Adjustable mounting bracket on top of the unit with 2 slotted holes
    • 2 slotted holes in the rear wall of the casing, below the heat exchanger
  • Power consumption and connection dimensioning
    • Electrical power consumption of the entire unit at nominal volume flow 250 m³/h < 44 W
    • For dimensioning the connecting cable: Take into account a connected load of 226 VA
  • Integrated cross-flow heat recovery unit:
    • Seawater-resistant aluminium design
    • High efficiency: Heat recovery efficiency > 52 %
    • Including condensate collection and drainage
  • With electromotive bypass:
    • Allows a partial airflow to bypass the heat recovery unit
    • Actuator 24 V (modulating) 0 – 100 %
    • Control via the unit-integrated single-room control
  • Outdoor air filter as Mini Pleat filter class ePM1 (fine dust filter):
    • Filter class according to ISO16890: ISO ePM1 65%
    • Eurovent-certified
    • Made from high-quality, wet-strength glass fibre paper
    • In tight pleats
    • Spacer:
      • Made from thermoplastic hot-melt adhesive
      • Even distance between the pleats (4 mm)
    • Frame made of moisture-resistant nonwoven fabric with pull-out tabs
    • The frame must not reduce the airflow cross-section (filter size = airflow cross-section)
    • Filter area ≥ 2.96 m²
  • Extract air filter (coarse dust filter) as flat filter medium, filter class according to ISO 16890: ISO Coarse 75 %

Sizing data
2
  • 2-pipe aluminium copper tube heat exchanger for air heating:
    • Adapted to the project-specific data
    • Easily removable for cleaning (the on-site connection to the main pipework is crucial, not included in the TROX scope of delivery)
    • Drain and vent option for each heating/cooling circuit
  • Cleaning the heat exchanger:
    • For easy removal: We recommend a connection to the on-site pipe network with flexible hoses (not included in the TROX scope of supply)
    • Connection points are the heat exchanger connections, ½" flat-sealing with union nut
  • Connection point to the on-site heating/plumbing system:
    • Pre-assembled hand-tight control components
    • Connection with external thread ½" flat-sealing
      • In the return flow: Valve including actuator
      • In the supply flow: Lockshield

KO

  • Easy-to-clean condensate drip tray without condensate drain: made of galvanised sheet steel, powder-coated (RAL 9005)

KM

  • Easy-to-clean condensate drip tray with condensate drain: Ø 12 x 1 mm made of galvanised sheet steel, powdercoated (RAL 9005)

Nominal size
  • Width: approx. 397 mm
  • Height: approx. 2160 mm (without levelling feet, without fixing bracket)
  • Depth: approx. 359 mm (without façade seal)

C3
With FSL-CONTROL III:
  • Single room controller for DIN rail mounting in the unit or in a separate control casing
  • Integrated microSD card as flash memory medium
    • At least 2 GB storage space
    • Saves the trend data
    • Accessible via RJ45 connection socket
  • For simple master-slave communication via Modbus RTU
  • Connection of up to 10 slave units to one master unit
  • Software:
    • 3 operating modes: Off, Automatic, Manual mode
    • 3 operating states: Occupied, Unoccupied, Standby
    • 4 operating state overrides: Boost, Class, night purge, fan forced circuit
  • Basic distinction between room temperature control by controlling heating and cooling valves or modulating bypass damper, or supply air temperature control for isothermal ventilation operation
  • Year-round heat recovery use

MA
Control function Master
  • Software package specially developed for decentralised ventilation units
  • Factory-equipped
  • Configured for master units
  • 42 digital or analogue inputs and outputs
  • CO2-guided air quality control
  • Alarm messages: Type A (shutdowns) and Type B (notifications)

SL
Control function Slave

  • Software package specially developed for decentralised ventilation units
  • Factory-equipped
  • 28 digital or analogue inputs and outputs

T
Only with control function MA
Real-Time-Clock (RTC):
  • Part of the master software package
  • Includes a simple time programme
    • 7 days with 10 switching points each
    • Automatic switching between summer and winter time
    • Night purge schedules

MT

With Modbus TCP

Modbus TCP interface (Ethernet):

  • FSL-CONTROL III can be integrated into an on-site MCE/BACS via the Modbus TCP protocol.
  • Required for visualisation via the X-TAIRMINAL
  • Additionally including web server for simplified configuration, commissioning and remote monitoring of the device.

BI

With BACnet IP

BACnet IP interface (Ethernet):

  • FSL-CONTROL III can be integrated into an on-site MCE/BACS via BACnet IP protocol.
  • Additionally including web server for simplified configuration, commissioning and remote monitoring of the device.

MR

Only with control function MA

With Modbus RTU

Modbus RTU interface (RS 485):

  • FSL-CONTROL III can be integrated into an on-site MCE/BACS via Modbus RTU

BM

Only with control function MA

With BACnet MS/TP

BACnet MS/TP interface (RS485):

  • FSL-CONTROL III can be integrated into an on-site MCE/BACS via BACnet MS/TP

C

Only with control function MA
Air quality sensor
With CO2sensor:

  • Component of the master unit
  • Sensor located in the extract air intake to monitor indoor air quality and control the outdoor air volume flow accordingly.
  • Measurement via an NDIR sensor that works on an infrared basis and compensates for any contamination through its 2-beam measuring principle
  • Measuring range 0 – 2000 ppm

V
Only with control function MA
Air quality sensor
With VOC sensor

  • Detection of a wide range of VOC emissions correlating with the CO2concentration in indoor air
  • TVOC mit auto-calibration
  • Detected indoor air substances include alcohols, aldehydes, aliphatic hydrocarbons, amines, aromatic hydrocarbons, CO, CH4, liquid gas, ketones, organic acids
  • Detection range: 0 – 2000 ppm, VOC and CO2equivalent
  • Self-test and automatic zero-point adjustment

Z
With supply air temperature sensor
  • Supply air temperature sensor with NTC thermistor sensing element
    • Resistance 10 kΩ at 25 °C
    • Measuring range -35 – 105 °C
    • Very short response time due to perforated measuring tip

A
With outside air temperature sensor (only with MA control function)

  • Outdoor air temperature sensor with NTC thermistor sensing element
    • Resistance 10 kΩ at 25 °C
    • Measuring range -35 – 105 °C

HV
Thermoelectric valve actuator:

  • For opening and closing valves
    • With position indicator
    • Including plug-in connecting cable
    • Supply voltage: 24 V DC
    • Control voltage 0 – 10 V DC
    • Power consumption 1 W
    • Protection rating: IP 54

HVE

Electromotive valve actuator

  • For opening and closing valves
    • Supply voltage 24 V AC/DC
    • Power consumption max. 2.5 VA
    • Control signal 3-point DC 0 – 10 V
    • Permissible media temperature 1 – 110 °C

R
Lockshield

  • For regulation and shut-off
    • Valve casing: straight way
    • External thread on both sides ½" flat sealing
    • Hand-tightened pre-assembled
    • Nominal width DN 15
    • Maximum media temperature 120 °C

0.25

Straight-through small valve:

  • Straight-through valve body
    • Male thread on both sides ½" flat sealing
    • Pre-assembled hand-tight
    • PN 16
    • DN 10
    • Kvs value 0.25
    • Media temperature 1 – 110 °C

0.40
Straight-through small valve:
  • Straight-through valve body
    • Male thread on both sides ½" flat sealing
    • Pre-assembled hand-tight
    • PN 16
    • DN 10
    • Kvs value 0.40
    • Media temperature 1 – 110 °C

0.63

Straight-through small valve:

  • Straight-through valve body
    • Male thread on both sides ½" flat sealing
    • Pre-assembled hand-tight
    • PN 16
    • DN 10
    • Kvs value 0.63
    • Media temperature 1 – 110 °C

1.00
Straight-through small valve:

  • Straight-through valve body
    • Male thread on both sides ½" flat sealing
    • Pre-assembled hand-tight
    • PN 16
    • DN 10
    • Kvs value 1.00
    • Media temperature 1 – 110 °C

F0.50

Pressure-independent control valve

  • Straight-through valve body
    • Male thread on both sides ½" flat sealing
    • Pre-assembled hand-tight
    • With modulating Open-Close control in combination with an externally adjustable, dynamic volume flow controller
    • With full valve authority
    • Nominal width DN 10
    • Media temperature 0 – 120 °C

Replacement filter set

  • Extract air filter: Filter pad
  • Outdoor air filter: Mini-Pleat-Filter

SA-V21KO / 397 × 2160 × 359 / C3MAT / MR / C / Z / A / HVR0,40
||||||||||||||||
12345678910111213141516


1 Type
SA-V vertical decentralised ventilation unit X-CUBE/SCHOOLAIR-V

2 Variant
No entry: Standard

3 Heat exchanger
2 2-pipe

4 Heat exchanger construction
Specify construction (technical design with TROX EPF or TROX CONFIGURATOR)

5 Construction
KO without condensate drain
KM with condensate drain

6 Nominal size [mm]
Width x height x depth
397 x 2160 x 359

7 Control system
OR without control system
C3 with FSL-CONTROL III

8 Control function
MA Master
SL Slave

9 Real-time clock
Only with control function MA
No entry: without real time clock
T with real time clock

10 Interface
No entry: without interface
MT with Modbus TCP
MR with Modbus RTU (only with control function MA)
BI with BACnet IP
BM with BACnet MS/TP (only with control function MA)

11 Air quality sensor
Only with control function MA
No entry: without air quality sensor
C with CO2 sensor
V with VOC sensor

12 Supply air temperature sensor
Z with supply air temperature sensor

13 Outdoor air temperature sensor
Only with control function MA
No entry: without outdoor air temperature sensor
A with outdoor air temperature sensor

14 Heating valve
HV with thermoelectric actuator
HVE with electromotive actuator

15 Lockshield – heating circuit
R with lockshield

16 Kvs value heating valve
0.25 (straight-way valve)
0.40 (straight-way valve)
0.63 (straight-way valve)
1.00 (straight-way valve)
F0.50 (pressure-independent control valve)

Order example: SA-V-2-1-KO/397x2160x359/C3-MA-T/MR/C/Z/A/HV-R-0.40

TypeSA-VVentilation unit for ceiling installation X-CUBE/SCHOOLAIR-V
Variant-Standard
Heat exchanger22-pipe
Heat exchanger construction1Heat exchanger type 1
ConstructionKOwithout condensate drain
Nominal size [mm]397×2160×359Width 397, height 2160, depth 359
Control systemC3with FSL-CONTROL III
Control functionMAMaster
Real time clockTwith real time clock
InterfaceMRwith Modbus RTU
Air quality sensorCwith COsensor
Supply air temperature sensorZwith supply air temperature sensor
Outdoor air temperature sensorAwith outdoor air temperature sensor
Heating valveHVwith thermoelectric actuator
Lockshield heating circuitRwith lockshield
Kvs value heating valve0.400.40 (straight-way valve)

Téléchargements

Information produit

Brochures

Certificats

Manuels d'utilisation

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"1; mode=block", "x-content-type-options"=>"nosniff", "x-download-options"=>"noopen", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8"}

Partager la page

Recommander cette page

Recommander cette page en envoyant un lien par mail.

Les champs marqués d'un (*) sont obligatoires.

Partager la page

Merci pour votre recommandation !

Votre recommandation a été envoyée et devrait arriver dans les plus brefs délais.

Contact

Nous sommes à votre disposition

Veuillez préciser votre message et le type de demande
Tel.: +32 (0) 2/522 07 80

Les champs marqués d'un (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +32 (0) 2/522 07 80

Contact

Nous sommes à votre disposition

Veuillez préciser votre message et le type de demande
Tel.: +32 (0) 2/522 07 80

Pièce jointe (max. 10MB)

Les champs marqués d'un (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +32 (0) 2/522 07 80