SA-V-2L

Tested to VDI 6022

X-CUBE_img_55
Cross flow heat recovery unit
SCHOOLAIR-V_img_173236

Water connections

SCHOOLAIR-V_img_173241

Filter change

SCHOOLAIR-B_img_127933

Levelling foot

SA-V-2L
X-CUBE_img_55
SCHOOLAIR-V_img_173236
SCHOOLAIR-V_img_173241
SCHOOLAIR-B_img_127933

X-CUBE SCHOOLAIR-V-2L

Supply and extract air unit for vertical installation on the façade

Ready-to-connect decentralised ventilation unit for comfortable room temperature control and supply and extract ventilation of rooms such as classrooms, meeting rooms and day-care centres
■ Installation possible during normal school operation
■ Acoustically optimised EC fans with low specific fan power, according to DIN EN 16798-3 SFP = 0
■ Switch-over option to secondary air mode
■ Reduction of fine dust and pollen through integrated air filters in accordance with VDI 6022 – filter class ISO ePM1 65% and extract air ISO coarse 75%
■ Tool-free filter replacement
■ Cross flow heat recovery unit
■ Optional year-round heat recovery operation
■ Highly efficient heat exchanger for heating or cooling as a 2-pipe system
■ Heat exchanger connection on the right-hand side, when viewed from the room
■ Condensate drip tray with or without condensate drain connection
■ Motorised shut-off dampers, normally closed

Optional equipment and accessories
■ Control system FSL-CONTROL III, specially designed and modularly constructed for decentralised ventilation systems
■ Wood panelling in various colours, including TROX ventilation grilles for supply and extract air (self-assembly kit)

Allgemeine Informationen

Functional description

Decentralised supply and extract air units ventilate the room and cover the cooling and heating load in accordance with the technical data. An EC centrifugal fan takes in the outdoor air which then flows through the motorised shut-off damper and the outdoor air filter.
The outdoor air then flows through the cross flow heat recovery unit, which can be switched off if it is more energy efficient. If necessary, the air is heated by the heat exchanger before it is discharged to the room as a displacement flow.
The extract air first passes through the extract air filter, then flows through the heat recovery unit, the extract air fan and the motorised shut-off damper before it is discharged to the outside as exhaust air.
If the indoor air quality is sufficient, the FSL-CONTROL III control system switches to energy-efficient secondary air mode by closing the outdoor air dampers. The control system compares the room air quality setpoint value to the actual value measured by the COsensor and switches automatically between outdoor air and secondary air operation.
In case of a power failure, the outdoor air and exhaust air dampers are closed to ensure fire protection, frost protection and to avoid draughts. This is ensured by a capacitor in each actuator.
Near the external wall, the supply air is discharged into the room with a medium velocity between 0.5 and 0.8 m/s. Due to the induction effect, the supply air velocity is rapidly reduced after entering the room. As a result, in cooling mode, the supply air spreads out like displacement flow over the entire floor area. Near heat sources such as people or equipment, a lift current is formed by natural convection, so that the air is exchanged primarily in these areas.

Information technique

  • FUNCTION
  • TECHNICAL DATA
  • ORDER CODE

Functional description
Decentralised supply and extract air units ventilate the room and cover the cooling and heating loads in accordance with the technical data. An EC centrifugal fan draws in the outdoor air, which flows through the motorised shut-off damper and the outdoor air filter. The outdoor air then passes through the crossflow heat recovery unit, which can be switched off under operating conditions where heat recovery is not required. If required, the air is heated by the heat exchanger before being discharged into the room as a displacement flow. The extract air passes through the extract air filter, before being discharged to the outside as exhaust air, via the cross-flow heat recovery unit, the extract air fan and the motorised shut-off damper. If the indoor air quality is adequate, the FSL-CONTROL III control system switches to energy-efficient secondary air mode by closing the outdoor air dampers. The control system compares the room air quality setpoints to the actual values measured by the CO2 sensor and switches automatically between outdoor air and secondary air operation. In case of a power failure, the outdoor air and exhaust air dampers are closed to ensure fire protection, frost protection, and to avoid draughts. This function is ensured by a capacitor in each actuator. The supply air flows into the room close to the façade at an average velocity of 0.5 – 0.8 m/s. As a result of the induction effect, the air velocity is rapidly reduced shortly after the air enters the room. As a result, in cooling mode the supply air spreads across the entire floor area as displacement flow. At heat sources such as people or equipment, natural convection creates a buoyant airflow, so that air exchange primarily occurs in these areas.

Width

397 mm

Height

2160 mm

Depth

359 mm

Volume flow rate

150, 200, 250 m³/h (boost 320 m³/h)

nominal volume flow rate

250 m³/h

Sound power level

31 – 46 dB(A)

Heat recovery efficiency

52 %

Maximum operating pressure, water side

6 bar

Maximum operating temperature

75 °C

Supply voltage

1~ 230 V AC, ±10 %, 50/60 Hz

Power rating

226 VA

Weight

70 kg

SA-V21KO / 397 × 2160 × 359 / C3MAT / MR / C / Z / A / HVR0,40
||||||||||||||||
12345678910111213141516


1 Type
SA-V vertical decentralised ventilation unit X-CUBE/SCHOOLAIR-V

2 Variant
No entry: Standard

3 Heat exchanger
2 2-pipe

4 Heat exchanger construction
Specify construction (technical design with TROX EPF or TROX CONFIGURATOR)

5 Construction
KO without condensate drain
KM with condensate drain

6 Nominal size [mm]
Width x height x depth
397 x 2160 x 359

7 Control system
OR without control system
C3 with FSL-CONTROL III

8 Control function
MA Master
SL Slave

9 Real-time clock
Only with control function MA
No entry: without real time clock
T with real time clock

10 Interface
No entry: without interface
MT with Modbus TCP
MR with Modbus RTU (only with control function MA)
BI with BACnet IP
BM with BACnet MS/TP (only with control function MA)

11 Air quality sensor
Only with control function MA
No entry: without air quality sensor
C with CO2 sensor
V with VOC sensor

12 Supply air temperature sensor
Z with supply air temperature sensor

13 Outdoor air temperature sensor
Only with control function MA
No entry: without outdoor air temperature sensor
A with outdoor air temperature sensor

14 Heating valve
HV with thermoelectric actuator
HVE with electromotive actuator

15 Lockshield – heating circuit
R with lockshield

16 Kvs value heating valve
0.25 (straight-way valve)
0.40 (straight-way valve)
0.63 (straight-way valve)
1.00 (straight-way valve)
F0.50 (pressure-independent control valve)

Order example: SA-V-2-1-KO/397x2160x359/C3-MA-T/MR/C/Z/A/HV-R-0.40

TypeSA-VVentilation unit for ceiling installation X-CUBE/SCHOOLAIR-V
Variant-Standard
Heat exchanger22-pipe
Heat exchanger construction1Heat exchanger type 1
ConstructionKOwithout condensate drain
Nominal size [mm]397×2160×359Width 397, height 2160, depth 359
Control systemC3with FSL-CONTROL III
Control functionMAMaster
Real time clockTwith real time clock
InterfaceMRwith Modbus RTU
Air quality sensorCwith COsensor
Supply air temperature sensorZwith supply air temperature sensor
Outdoor air temperature sensorAwith outdoor air temperature sensor
Heating valveHVwith thermoelectric actuator
Lockshield heating circuitRwith lockshield
Kvs value heating valve0.400.40 (straight-way valve)

Téléchargements

Information produit

Brochures

Certificats

Manuels d'utilisation

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"0", "x-content-type-options"=>"nosniff", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8", "link"=>"</assets/application-efbc495b06ca980ef13dc743756002fce2f413f798fecb64c7f0c81954c16402.css>; rel=preload; as=style; nopush,</assets/print-fec2e47d6d8dcc5d4c101139f17046ba981ca1c12f71e7e403fba50cc7584175.css>; rel=preload; as=style; nopush,</assets/other_js/modernizr.custom.93544-c26374a79d804901074bb4aa6fd3fa44ea22e840389915d2adce16b024021ef3.js>; rel=preload; as=script; nopush,</assets/other_js/js.cookie.min-de103d86d1919b40950f791699b4ce768137fde41af09b35ff92bde369732183.js>; rel=preload; as=script; nopush,</assets/other_js/jquery-3.5.1-2c4ce18a1a3f144c333912efc24a76c9a165a0dba9f88a499985df1af0a196a2.js>; rel=preload; as=script; nopush"}

Partager la page

Recommander cette page

Recommander cette page en envoyant un lien par mail.

Les champs marqués d'un (*) sont obligatoires.

Partager la page

Merci pour votre recommandation !

Votre recommandation a été envoyée et devrait arriver dans les plus brefs délais.

Contact

Nous sommes à votre disposition

Veuillez préciser votre message et le type de demande
Tel.: +32 (0) 2/522 07 80

Pièce jointe (max. 10MB)

Les champs marqués d'un (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +32 (0) 2/522 07 80

Contact

Nous sommes à votre disposition

Veuillez préciser votre message et le type de demande
Tel.: +32 (0) 2/522 07 80

Pièce jointe (max. 10MB)

Les champs marqués d'un (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +32 (0) 2/522 07 80