X-SENS

Sensors for X-AIRCONTROL zone modules and other equipment

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

  • Combined temperature and humidity sensor
  • Dew point monitor
  • Air quality sensor
  • Motion detector
  • Splitter

Application

Application

  • Type X-SENS sensors for use with X-AIRCONTROL and other control systems
  • Can be connected to X-AIR-ZMO zone modules and X-AIR-ZMAS master modules
  • Duct temperature sensor for supply and extract air
  • Combined temperature and humidity sensor for extract air ducts
  • Air quality sensor used as a duct sensor for measuring the concentration of volatile organic compounds (VOC)
  • Air quality sensor for measuring the CO2 content in the room air and, when used as a room sensor, for measuring the humidity
  • Dew point monitor for chilled ceilings etc.
  • Motion detector (occupancy)
  • Four-way splitter for the connection of four sensors or control panels (Modbus)

Description

Variants

  • TEMP-RH-EXH: Combined temperature and humidity sensor for extract air
  • TEMP-PT1000: Duct temperature sensor (PT1000)
  • VOC: Air quality sensor (VOC)
  • CO2-RH: Combined CO2 and humidity sensor
  • DEWPT: Dew point monitor
  • PIR-SM: 180° motion detector
  • PIR-FM: 360° motion detector
  • SPLITTER: Four-way splitter for the connection of four sensors or control panels (Modbus)

Maintenance

  • Maintenance-free as construction and materials are not subject to wear
  • Checking and cleaning is recommended, in particular if the device is used in a room or in an extract air duct
  • Regular cleaning from dust is recommended

Information technique

Function, Technical data, Specification text, Order code

  • Function
  • Technical data
  • Specification text
  • Order code
X-AIRCONTROL zone 00236861_0
① Zone module
② Temperature sensor
③ Air quality sensor
④ Motion detector
⑤ Humidity sensor
⑥ Control panel
⑦ Cooling, e.g. with an active chilled beam
⑧ Heating, e.g. with a heating coil
⑨ Volume flow control


Combined temperature and humidity sensor

Functional description

X-SENS-TEMP-RH-EXH sensors are control components for integration with control systems such as X-AIRCONTROL.

The sensor consists of two sensor heads for measuring temperature and relative humidity. The duct sensor variant is intended for use in circular or rectangular extract air ducts.

Measuring ranges are –40 to 120 °C and 0 to 100% relative humidity.

A Modbus RTU data interface is used to transmit measured values to the control system.

A plug-in connection cable with an RJ12 plug simplifies installation.

The zone module automatically recognises the sensor (plug and play).

Duct temperature sensor (PT1000)

Functional description

X-SENS-TEMP-PT1000 temperature sensors are control components for integration with control systems such as X-AIRCONTROL.

The temperature sensor is a PT1000 sensor. The duct sensor variant is intended for use in circular or rectangular supply air ducts, or preferably in extract air ducts, as an alternative to a room temperature sensor.

Measuring range: –40 to 85 °C.

The zone module automatically recognises the temperature sensor (plug and play).

Air quality sensor (VOC)

Functional description

X-SENS-VOC air quality sensors are control components for integration with control systems such as X-AIRCONTROL.

The air quality sensor measures the concentration of volatile organic compounds such as alcohols, aldehydes, ketones, esters, terpenes, aromatic compounds, and alkenes. The duct sensor variant is intended for use in circular or rectangular extract air ducts.

Measuring range: 450 to 2000 ppm.

A Modbus RTU data interface is used to transmit measured values to the control system.

A plug-in connection cable with an RJ12 plug simplifies installation.

The zone module automatically recognises the sensor (plug and play).

Combined CO2 and humidity sensor

Functional description

X-SENS-CO2-RH sensors are control components for integration with control systems such as X-AIRCONTROL.

The sensor consists of two sensor heads for measuring CO2 concentration and relative humidity. The room sensor variant is intended for use in a room. The precision of CO2 concentration measurements is maintained by cyclical self calibration.

Measuring ranges are 0 to 2000 ppm and 0 to 100% relative humidity.

Measured values are transmitted to the control system via 0 – 10 V DC analogue signals.

The zone module automatically recognises the sensor (plug and play).

180° motion detector

Functional description

X-SENS-PIR-SM motion detectors are control components for integration with control systems such as X-AIRCONTROL.

The motion detector includes a PIR sensor (passive infrared) for detectiong people in a room, i.e. occupancy. The flush mounted variant for mounting on a wall has an operational range of 180°.

The condition (i.e. if the room is occupied or not) is transmitted to the control system via a volt-free digital output.

360° motion detector

Functional description

X-SENS-PIR-FM motion detectors are control components for integration with control systems such as X-AIRCONTROL.

The motion detector includes a PIR sensor (passive infrared) for detectiong people in a room, i.e. occupancy. The surface mounted variant for mounting on a ceiling has an operational range of 360°.

The condition (i.e. if the room is occupied or not) is transmitted to the control system via a volt-free digital output.

Dew point monitor

Functional description

X-SENS-DEWPT dew point monitors are control components for integration with control systems such as X-AIRCONTROL.

The dew point monitor contains a humidity sensor for measuring the relative humidity near the dew point (100% rh). The goal is to ensure that the dew point is not reached, i.e. that condensation is avoided.

The condition is transmitted to the control system via a volt-free digital output.

Four-way splitter

Functional description

X-SENS-SPLITTER four-way splitters are used to connect up to three sensors and actuators to an interface, e.g. to an interface of a zone module within X-AIRCONTROL.

The four-way splitter can also serve as an adapter to connect air quality and temperature sensors to terminals in case the connection cables have bare wire ends. The actual connection to the zone modules is done with RJ12 plugs.

X-SENS-TEMP-RH-EXH

Supply voltage

24 V DC ± 25%, from the zone module

Power rating

0.22 W


Temperature measurement

Measuring range

–40 to 120 °C

Measurement error

0.25 K (15 – 40 °C)


Humidity measurement

Measuring range

0 – 100% rh

Measurement error

<5% rh, <2% rh (10 – 90% rh)

Long term drift

0.5% rh per year

Installed length

50 – 250 mm

Operating temperature

– 20 to 50 °C

Max. humidity

5 – 95% rh, no condensation

IEC protection class

III (protective extra-low voltage)

Protection level

IP 54 (sensor head IP 32)

Connecting cable

7 m, with RJ12 plug

Installation location

Circular and rectangular ducts

Weight

250 g


X-SENS-TEMP-PT1000

Sensor

PT1000

Resistance

1000 Ω at 0 °C

Measurement error

0.5 K (–40 to 15 °C) 0.725 K (40 to 85 °C)

Installed length

116 mm

Operating temperature

– 40 to 100 °C

Max. humidity

5 – 95% rh, no condensation

IEC protection class

III (protective extra-low voltage)

Protection level

IP 32

Connecting cable

4 m, bare wire ends

Installation location

Circular and rectangular ducts

Weight

250 g


X-SENS-VOC

Supply voltage

24 V DC ± 25%, from the zone module

Power rating

0.46 W

Measuring range

450 – 2000 ppm

Measurement error

<150 ppm

Start-up time

15 min

Response time

5 min

Installed length

65 – 105 mm

Operating temperature

0 – 50 °C

Max. humidity

5 – 95% rh, no condensation

IEC protection class

III (protective extra-low voltage)

Protection level

IP 54 (sensor head IP 20)

Connecting cable

7 m, with RJ12 plug

Installation location

Circular and rectangular ducts

Weight

175 g


X-SENS-CO2-RH

Supply voltage

24 V AC/DC, from the zone module

Power rating

1.2 W


CO2 measurement

Measuring range

0 – 2000 ppm

Measurement error

±30 ppm

Start-up time

10 min


Humidity measurement

Measuring range

0 – 100% rh

Measurement error

3% rh (20 – 80% rh)

Long term drift

<10% rh per year

Operating temperature

0 – 50 °C

Max. humidity

5 – 95% rh, no condensation

IEC protection class

III (protective extra-low voltage)

Protection level

IP 30

Colour

RAL 9010, pure white

Installation location

Wall installation

Dimensions

80 × 105 × 23.5 mm

Weight

69 g


X-SENS-PIR-SM

Supply voltage

24 V AC/DC ± 10%, from the zone module

Sensor

PIR (passive infrared)

Operational range

180°

Detection range

8 m; 4 m with people sitting

Installation, distance from floor

1.1 to 2.2 m (4 m max.)

Operating temperature

– 25 to 55 °C

Max. humidity

5 – 95% rh, no condensation

IEC protection class

III (protective extra-low voltage)

Protection level

IP 30

Connection

Screw terminals

Colour

RAL 9010, pure white

Installation location

Wall installation on a Ø60 mm junction box

Dimensions

88 × 88 × 64 mm

Weight

98 g


X-SENS-PIR-FM

Supply voltage

24 V AC/DC ± 10%, from the zone module

Sensor

PIR (passive infrared)

Operational range

360°

Detection range

8 m; 4 m with people sitting

Installation, distance from floor

2.5 to 3.0 m (10 m max.)

Operating temperature

– 25 to 55 °C

Max. humidity

5 – 95% rh, no condensation

IEC protection class

III (protective extra-low voltage)

Protection level

IP 30

Connection

Screw terminals

Colour

RAL 9010, pure white

Installation location

Wall installation

Dimensions

98 mm, 48 mm protruding beyond the surface

Weight

104 g


X-SENS-DEWPT

Supply voltage

24 V AC/DC ± 20%, from the zone module

Power rating

1.0 VA

Switching point

92 ±4% rh at 25 °C

Hysteresis

5% rh

Response time

3 minutes max.

Exposure to condensation

30 minutes max.

Switch output

Volt-free contact, 230 V AC max., 1 A max.

Operating temperature

0 – 50 °C

IEC protection class

III (protective extra-low voltage)

Protection level

IP 30

Installation location

Casing suitable for installation on a wall or ceiling, sensor casing suitable for chilled surfaces

Weight

85 g


X-SENS-SPLITTER

Operating temperature

0 to 50 °C

IEC protection class

III (protective extra-low voltage)

Protection level

IP 20

Connection

4 RJ12 sockets and 8 spring-loaded terminals, 1.5 mm²

Installation location

Switch cabinet, wall or ceiling

Fixing

On a mounting rail

Dimensions

46 × 78 × 45

Weight

60 g


Combined temperature and humidity sensor

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

Combined temperature and humidity sensor for rectangular and circular extract air ducts.

Ready-to-operate sensor which consists of a casing with flange, a protective tube with two sensor heads, and a connecting cable with RJ12 plug.

Modbus RTU data interface for the transmission of measured values to the control system.

The zone module automatically recognises the sensor (plug and play).

Materials and surfaces

  • Plastic casing

Technical data

  • Supply voltage: 24 V DC ± 25%, from the zone module
  • Power rating: 0.22 VA

Temperature measurement

  • Measuring range: –40 to 120 °C
  • Measurement error: 0.25 K (15 to 40 °C)

Humidity measurement

  • Measuring range: 0 to 100% rh
  • Measurement error: <5 % rh, <2 % rh (10 to 90% rh)
  • Long term drift: 0.5% rh per year


  • Installed length: 50 to 250 mm
  • Operating temperature: –20 to 50 °C
  • Max. humidity: 5 to 95% rh, no condensation
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 54 (sensor head IP 32)
  • Connecting cable: 7 m, with RJ12 plug
  • Installation location: Circular and rectangular ducts

Duct temperature sensor (PT1000)

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

Temperature sensor for rectangular and circular extract air ducts.

Ready-to-operate sensor which consists of a protective tube with flange, a sensor head and a connecting cable.

The zone module automatically recognises the temperature sensor (plug and play).

Materials and surfaces

  • Protective tube made of plastic

Technical data

  • Supply voltage from the zone module
  • Sensor: PT1000
  • Resistance: 1000 Ω at 0 °C
  • Measurement error: 0.5 K (–40 to 15 °C), 0.725 K (40 to 85 °C)
  • Installed length: 116 mm
  • Operating temperature: –40 to 100 °C
  • Max. humidity: 5 to 95% rh, no condensation
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 32
  • Connecting cable: 4 m, bare wire ends
  • Installation location: Circular and rectangular ducts

Air quality sensor (VOC)

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

Sensor for measuring the concentration of volatile organic compounds in rectangular and circular supply or extract air ducts.

Ready-to-operate sensor which consists of a protective tube with flange, a sensor head, and a connecting cable with RJ12 plug.

Modbus RTU data interface for the transmission of measured values to the control system.

The zone module automatically recognises the temperature sensor (plug and play).

Materials and surfaces

  • Plastic casing

Technical data

  • Supply voltage: 24 V DC ± 25%, from the zone module
  • Power rating: 0.46 VA
  • Measuring range: 450 to 2000 ppm
  • Measurement error: <150 ppm
  • Start-up time: 15 minutes
  • Response time: 5 minutes
  • Installed length: 65 to 105 mm
  • Operating temperature: 0 to 50 °C
  • Max. humidity: 5 – 95% rh, no condensation
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 54 (sensor head IP 20)
  • Connecting cable: 7 m, with RJ12 plug
  • Installation location: Circular and rectangular ducts

Combined CO2 and humidity sensor

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

Sensor for measuring the CO2 concentration and humidity in rooms.

Ready-to-operate sensor which consists of a casing with two sensor heads and connection terminals.

The zone module automatically recognises the sensor (plug and play).

Materials and surfaces

  • Plastic casing

Technical data

  • Supply voltage: 24 V AC/DC, from the zone module
  • Power rating: 1.2 VA

CO2 measurement

  • Measuring range: 0 to 2000 ppm
  • Measurement error: 30 ppm
  • Start-up time: 10 minutes

Humidity measurement

  • Measuring range: 0 to 100% rh
  • Measurement error: 3% rh (20 to 80% rh)
  • Long term drift: <10% rh per year


  • Operating temperature: 0 to 50 °C
  • Max. humidity: 5 to 95% rh, no condensation
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 30
  • Colour: RAL 9010, pure white
  • Installation location: Wall
  • Dimensions: 80 × 105 × 23.5 mm

180° motion detector

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

Motion detector (occupancy).

Ready-to-operate detector which consists of a casing and a PIR sensor (passive infrared).

Switch output (volt-free contact) for the transmission of the detected condition (occupied or not occupied) to the control system.

Materials and surfaces

  • White plastic casing

Technical data

  • Supply voltage: 24 V AC/DC ± 10%, from the zone module
  • Sensor: PIR (passive infrared)
  • Operational range: 180°
  • Detection range: 8 m; 4 m with people sitting
  • Installation location: Preferably 1.1 to 2.2 m above the floor (4 m max.)
  • Operating temperature: –25 to 55 °C
  • Max. humidity: 5 to 95% rh, no condensation
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 30
  • Connection: Screw terminals
  • Colour: RAL 9010, pure white
  • Installation location: Wall installation on a Ø60 mm junction box
  • Dimensions: 88 × 88 × 64 mm

360° motion detector

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

Motion detector (occupancy).

Ready-to-operate detector which consists of a casing and a PIR sensor (passive infrared).

Switch output (volt-free contact) for the transmission of the detected condition (occupied or not occupied) to the control system.

Materials and surfaces

  • White plastic casing

Technical data

  • Supply voltage: 24 V AC/DC ± 10%, from the zone module
  • Sensor: PIR (passive infrared)
  • Operational range: 360°
  • Detection range: 8 m; 4 m with people sitting
  • Installation location: Preferably 2.5 to 3.0 m above the floor (10 m max.)
  • Operating temperature: –25 to 55 °C
  • Max. humidity: 5 to 95% rh, no condensation
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 30
  • Connection: Screw terminals
  • Colour: RAL 9010, pure white
  • Installation location: Wall
  • Dimensions: 98 mm, 48 mm protruding beyond the surface

Dew point monitor

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

Sensor for monitoring the dew point on chilled surfaces.

Ready-to-operate sensor which consists of a casing and a sensor head in a separate casing.

Switch output (volt-free contact) for the transmission of the detected condition (occupied or not occupied) to the control system.

Materials and surfaces

  • Plastic casing

Technical data

  • Supply voltage: 24 V AC/DC ± 20%, from the zone module
  • Power rating: 1.0 VA
  • Switching point: 92 ± 4% rh at 25 °C
  • Hysteresis: 5% rh
  • Response time: 3 minutes max.
  • Exposure to condensation: 30 minutes max.
  • Switch output: Volt-free, 230 V AC max. 1 A max.
  • Installation location: Casing suitable for installation on a wall or ceiling, sensor casing suitable for chilled surfaces

Four-way splitter

Components for the measurement and recording of various quantities and conditions in systems for single room control and centralised control – such as X-AIRCONTROL

Four-way splitter for the connection of four sensors or control panels (Modbus).

The four-way splitter can also serve as an adapter to connect air quality and temperature sensors to terminals in case the connection cables have bare wire ends. The actual connection to the zone modules is done with RJ12 plugs.

Materials and surfaces

  • Plastic casing

Technical data

  • Operating temperature: 0 to 50 °C
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 20
  • Connection: 4 RJ12 sockets and 8 spring-loaded terminals, 1.5 mm²
  • Installation location: Switch cabinet, wall or ceiling
  • Fixing: On a mounting rail
  • Dimensions: 46 × 78 × 45 mm

00229238_0

 Type
X-SENS       Sensor

 

 Variant
TEMP-RH-EXH       Combined temperature and humidity sensor for extract air
TEMP-PT1000       Duct temperature sensor (PT1000)
VOC       Air quality sensor (VOC)
CO2-RH       Combined CO2 and humidity sensor
DEWPT       Dew point monitor
PIR-SM       180° motion detector
PIR-FM       360° motion detector
SPLITTER       Four-way splitter for the connection of four sensors or control panels (Modbus)

 

Temperature sensor, Air quality sensor, Motion detector, Other

  • Temperature sensor
  • Air quality sensor
  • Motion detector
  • Other

X-SENS-TEMP-RH-EXH

Application

  • X-SENS-TEMP-RH-EXH temperature and humidity sensor to be used for X-AIRCONTROL or other systems; can be connected to X-AIR-ZMO zone modules
  • Temperature and relative humidity measurement
  • Sensor for rectangular and circular extract air ducts
  • Measuring ranges –40 to 120 °C and 0 to 100 % rh
  • Plug-in connection for supply voltage and for communication with the zone module
  • The zone module automatically recognises the sensor (plug and play)

Parts and characteristics

  • Casing with flange to be screw-fixed to the installation surface
  • Protective tube with sensor heads, for installation into a duct
  • Plug-in cable
  • Modbus RTU data interface

Materials and surfaces

  • Plastic casing

X-SENS-TEMP-PT1000

Application

  • X-SENS-TEMP-PT1000 temperature sensor to be used for X-AIRCONTROL or other systems; can be connected to X-AIR-ZMO zone modules
  • Temperature measurement
  • Sensor for rectangular and circular extract air ducts
  • Measuring range –40 to 85 °C
  • The zone module automatically recognises the temperature sensor (plug and play)

Parts and characteristics

  • Protective tube with sensor head and flange to be screw-fixed to the installation surface
  • Connecting cable

Materials and surfaces

  • Protective tube made of plastic

X-SENS-VOC

Application

  • X-SENS-VOC air quality sensor to be used for X-AIRCONTROL or other systems; can be connected to X-AIR-ZMO zone modules
  • Measurement of the concentration of volatile organic compounds
  • Sensor for rectangular and circular extract air ducts
  • Measuring range: 450 to 2000 ppm
  • Plug-in connection for supply voltage and for communication with the zone module
  • The zone module automatically recognises the air quality sensor (plug and play)

Parts and characteristics

  • Casing with flange to be screw-fixed to the installation surface
  • Protective tube with sensor head, for installation into a duct
  • Plug-in cable
  • Modbus RTU data interface

Materials and surfaces

  • Plastic casing

X-SENS-CO2-RH

Application

  • X-SENS-CO2-RH combination sensor to be used for X-AIRCONTROL or other systems; can be connected to X-AIR-ZMO zone modules
  • Measurement of the CO2 concentration and relative humidity
  • Room sensor for use inside a room
  • Measuring ranges 0 to 2000 ppm and 0 to 100% rh
  • The zone module automatically recognises the sensor (plug and play)

Parts and characteristics

  • Casing with sensors for surface mounting on walls
  • 0 – 10 V DC analogue signals

Materials and surfaces

  • Plastic casing

X-SENS-PIR-SM

Application

  • X-SENS-PIR-SM motion detectors to be used for X-AIRCONTROL or other systems; can be connected to X-AIR-ZMO zone modules
  • For detecting if there are people in a room (occupancy)
  • 180° operational range
  • Casing to be flush mounted into walls

Parts and characteristics

  • Casing with PIR sensor, to be flush mounted into walls
  • Volt-free digital output

Materials and surfaces

  • White plastic casing

X-SENS-PIR-FM

Application

  • X-SENS-PIR-SM motion detectors to be used for X-AIRCONTROL or other systems; can be connected to X-AIR-ZMO zone modules
  • For detecting if there are people in a room (occupancy)
  • 360° operational range
  • Casing to be surface mounted on ceilings

Parts and characteristics

  • Casing with PIR sensor to be surface mounted on ceilings
  • Volt-free digital output

Materials and surfaces

  • White plastic casing

X-SENS-DEWPT

Application

  • X-SENS-DEWPT dew point monitor to be used for X-AIRCONTROL or other systems; can be connected to X-AIR-ZMO zone modules
  • Dew point temperature monitoring
  • Sensor head for chilled ceilings
  • Switching point: 92% rh

Parts and characteristics

  • Casing to be surface mounted on walls
  • Separate sensor casing for chilled surfaces
  • Volt-free digital output

Materials and surfaces

  • Plastic casing

X-SENS-SPLITTER

Application

  • X-SENS-SPLITTER four-way splitter to be used with X-AIRCONTROL or other systems; used to connect sensors and control panels via Modbus
  • Adapter used to connect up to four components to terminals in case the connection cables have bare wire ends; also to connect RJ12 plugs.

Materials and surfaces

  • Plastic casing

Installation details, Basic information and nomenclature

  • Installation details

Installation and commissioning

X-SENS-TEMP-RH-EXH, X-SENS-TEMP-PT1000

  • Choose a suitable place for the sensor to mount it inside a duct
  • Use the cable to connect the sensor to the zone module
  • The zone module automatically recognises the sensor (plug and play)


X-SENS-VOC

  • Choose a suitable place for the air quality sensor to mount it inside a duct
  • Use the cable to connect the sensor to the zone module
  • The zone module automatically recognises the air quality sensor (plug and play)


X-SENS-CO2-RH

  • Mount the lower part of the casing to a junction box or to the wall
  • Connect the wires
  • Attach the upper part of the casing
  • The zone module automatically recognises the air quality sensor (plug and play)


X-SENS-PIR-SM

  • Ensure that the installation location is suitable for the 180° operational range and for the detection range
  • Wall installation: Preferably 1.1 to 2.2 m above the floor (4 m max.)
  • Connect the wires
  • Mount the lower part of the casing to a junction box or to the wall
  • Put the cover on
  • Configure the 'motion detector' function on the zone module


X-SENS-PIR-FM

  • Ensure that the installation location is suitable for the 360° operational range and for the detection range
  • Ceiling installation: Preferably 2.5 to 3.0 m above the floor (10 m max.)
  • Connect the wires
  • Fix the lower part of the casing to the ceiling
  • Attach the upper part of the casing and the cover plate
  • Configure the 'motion detector' function on the zone module


X-SENS-DEWPT

  • The sensor casing should be fixed in the coldest area of the chilled surface (measurement location)
  • The installation area may be flat or curved (chilled ceiling or circular duct)
  • Fix the casing to the wall
  • Connect the wires
  • Configure the 'dew point monitor' function on the zone module


X-SENS-SPLITTER

  • Mount the splitter onto a mounting rail
  • Plug in the data cable to the zone module (RJ12 plug)
  • Plug in the data cables to the sensors and actuators and to the control panel (RJ12)
  • The maximum cable length is 30 m.

Téléchargements

Information produit

Manuels d'utilisation

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://*.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://*.onventis.com http://localhost:63342 http://cerebrum.local https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Partager la page

Recommander cette page

Recommander cette page en envoyant un lien par mail.

Les champs marqués d'un (*) sont obligatoires.

Partager la page

Merci pour votre recommandation !

Votre recommandation a été envoyée et devrait arriver dans les plus brefs délais.

Contact

Nous sommes à votre disposition

Veuillez préciser votre message et le type de demande
Tel.: +32 (0) 2/522 07 80

Les champs marqués d'un (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +32 (0) 2/522 07 80

Contact

Nous sommes à votre disposition

Veuillez préciser votre message et le type de demande
Tel.: +32 (0) 2/522 07 80

Pièce jointe (max. 10MB)

Les champs marqués d'un (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +32 (0) 2/522 07 80