JZ-LL-AL_img_01psd.psd.link
Multileaf damper, variant JZ-LL-AL

Multileaf damper with actuator

JZ-LL-AL_img_02psd.psd.link
Opposed blades

Opposed blades

JZ-LL-AL_img_03psd.psd.link
Closed cell side seals

Closed cell side seals

JZ-LL-AL_img_04psd.psd.link
Encased gears

Encased gears

JZ-LL-AL_img_01psd.psd.link
JZ-LL-AL_img_02psd.psd.link
JZ-LL-AL_img_03psd.psd.link
JZ-LL-AL_img_04psd.psd.link

JZ-LL-AL  

Multileaf dampers made of aluminium for extremely low-leakage shut-off in ventilation and air conditioning systems

 


Rectangular multileaf dampers for volume flow and pressure control as well as for extremely low-leakage shut-off of ducts and openings in walls and ceiling slabs


  • Maximum dimensions 1200 × 1000 mm
  • Closed multileaf damper air leakage to EN 1751, class 4
  • Casing air leakage to EN 1751, class C
  • Aerofoil opposed action blades
  • Closed cell side seals meet increased hygiene requirements
  • Blades interconnected by gears
  • Available in standard sizes and many intermediate sizes

 


Optional equipment and accessories


  • Actuators: Open/close actuators, modulating actuators
  • Powder-coated construction
  • Anodised construction


 

General information

Application

  • Multileaf dampers as a control element in volume flow rate and differential pressure control in ventilation and air conditioning systems
  • For extremely low-leakage shut-off of ducts and openings in walls and ceiling slabs



Special features

  • Aerofoil blades
  • Low-maintenance, robust construction
  • No parts with silicone
  • Available in standard sizes and many intermediate sizes
  • Closed cell side seals meet increased hygiene requirements



Classification

Air leakage with closed multileaf damper according to EN 1751: test pressure up to 2000 Pa

  • Class 4



Nominal sizes

  • B: 200 – 1200 mm, in increments of 1 mm
  • H: 100, 150, 200, 250, 300, 350, 400, 450, 500, 550, 600, 650, 700, 750, 800, 850, 900, 950, 1000 mm
  • Any combination of B × H



Parts and characteristics

  • Ready-to-install shut-off damper
  • Blades with gears
  • Drive arm
  • Quadrant stay with blade position indicator
  • Operating temperature 0 to 60 °C



Attachments

  • Quadrant stays and limit switches for the infinite adjustment of the multileaf dampers and for capturing the end positions
  • Open/close actuators for opening and closing multileaf dampers
  • Modulating actuators for variable damper blade positions
  • Pneumatic actuators for opening and closing multileaf dampers



Accessories



  • Installation subframes for the fast and simple installation of multileaf dampers




Construction features

  • Rectangular casing, with screws, material thickness 1.5 mm
  • Blades, material thickness 1.25 mm
  • Flanges on both sides, suitable for duct connection, with corner holes
  • Encased gears on both blade ends
  • Damper blade shafts, Ø12 mm, with notch to indicate the damper blade position (not for attachment ZS99)
  • With drive shaft as an attachment: For the position of the drive shaft see 'Dimensions and weight'
  • With actuator as an attachment: The actuator position at the first blade from the top (with up to 3 blades) or at the third blade from the top (with 4 or more blades)
  • From H = 600 mm with 2 spindles, with linkage
  • Blade tip seals and side seals



Materials and surfaces



  • Casing and blades made of extruded aluminium sections
  • Blade shafts, bearing plate and drive arm made of galvanised steel
  • Linkage (from H = 600 mm) made of galvanised steel
  • Gears made of PBS plastic
  • Blade tip seals made of PE/PTV plastic
  • Side seals made of closed cell EVA foam
  • P1: Powder-coated, RAL CLASSIC colour
  • PS: Powder-coated, DB colour
  • S3: Anodised, colour according to EURAS standard, E6-C-0



Standards and guidelines

  • Casing air leakage to EN 1751, class C
  • Closed multileaf damper air leakage to EN 1751, class 4

  • Meets the increased requirements of DIN 1946, Part 4, with regard to the acceptable closed multileaf damper air leakage



Maintenance

  • Maintenance-free, as construction and materials are not subject to wear
  • Contamination should be removed as it may lead to corrosion and to increased closed multileaf damper air leakage

Information technique

Function, Technical data, Quick sizing, Specification text, Order code, Related products

  • Function
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE
  • RELATED PRODUCTS
Schematic illustration of JZ-LL-AL JZ-LL-AL_gc_01ai.png

① Casing

② Encased gears

③ Opposed blades

④ Side seal

⑤ Blade tip seal

⑥ Actuator

⑦ External linkage (from H = 600 mm)

⑧ Bearing plate with quadrant stay


Multileaf dampers with gears can only have opposed action blades.

The internal gears transfer the synchronous rotational movement from the drive arm to the individual blades.

 


The torque for closing a multileaf damper must be dimensioned so that the damper can be safely opened and closed. For closure, the torque must suffice to ensure complete shut-off by the blades. Opening is initiated without aerodynamic forces. When air flows through the damper, the aerodynamic forces of the airflow create a closing force (torque) on the blades; this happens independently of the direction of the airflow. This closing force must be countered, or overcome. The blade angle α with the largest torque depends, among other things, on the fan characteristics.
 

Nominal sizes200 × 100 mm – 1200 × 1000 mm
Maximum permitted static differential pressure for a closed multileaf damper2000 Pa
Operating temperature0 to 60 °C


 


Minimum torques [Nm]


HB
200400500600700800900100011001200
100 – 65010101010101010101010
700 – 100020202020202020202020


 


Free cross-sectional area [m²]


HB
200300400500600700800900100011001200
100, 1500.0140.0220.030.0380.0470.0550.0630.0710.0790.0870.095
200, 2500.0280.0450.0610.0770.0930.1090.1260.1420.1580.1740.19
300, 3500.0430.0670.0910.1150.140.1640.1880.2130.2370.2610.286
400, 4500.0570.0890.1220.1540.1860.2190.2510.2840.3160.3480.381
500, 5500.0710.1110.1520.1920.2330.2730.3140.3540.3950.4350.476
600, 6500.0850.1340.1820.2310.2790.3280.3770.4250.4740.5220.571
700, 7500.0990.1560.2130.2690.3260.3830.4390.4960.5530.610.666
800, 8500.1130.1780.2430.3080.3730.4370.5020.5670.6320.6970.761
900, 9500.1280.20.2730.3460.4190.4920.5650.6380.7110.7840.857
10000.1420.2230.3040.3850.4660.5470.6280.7090.790.8710.952

Intermediate sizes: Interpolate values between widths.



 

Sound power level for a closed multileaf damper LWA [dB(A)]

Δpt [Pa]

Area B × H [m²]

0.04

0.09

0.16

0.25

0.36

0.64

0.81

1

1.2

100<10<10<10<101012131415
200<101416171922222325
500222628303234353637
1000323537394143444546
1500374143444649505152
2000414447495153545556


 



Quick sizing tables provide a good overview of the sound power levels and differential pressures that can be expected. Approximate intermediate values can be interpolated. Precise intermediate values and spectral data can be calculated with our Easy Product Finder design program. The sound power levels LWA apply to multileaf dampers with a cross-sectional area (B × H) of 1 m². The differential pressures apply to multileaf dampers installed in ducts (installation type A).

Rectangular multileaf dampers for volume flow and pressure control as well as for low-leakage shut-off of ducts and openings in walls and ceiling slabs. Ready-to-operate unit which consists of the casing, aerofoil blades and the blade mechanism. Flanges on both sides, suitable for duct connection. The blade position is indicated externally by a notch in the blade shaft extension. Closed multileaf damper air leakage according to EN 1751, Class 4. Casing leakage according to EN 1751, Class C.




Special features

  • Aerofoil blades
  • Low-maintenance, robust construction
  • No parts with silicone
  • Available in standard sizes and many intermediate sizes
  • Closed cell side seals meet increased hygiene requirements



Materials and surfaces



  • Casing and blades made of extruded aluminium sections
  • Blade shafts, bearing plate and drive arm made of galvanised steel
  • Linkage (from H = 600 mm) made of galvanised steel
  • Gears made of PBS plastic
  • Blade tip seals made of PE/PTV plastic
  • Side seals made of closed cell EVA foam
  • P1: Powder-coated, RAL CLASSIC colour
  • PS: Powder-coated, DB colour
  • S3: Anodised, colour according to EURAS standard, E6-C-0



Technical data



  • Nominal sizes: 200 × 100 mm – 1200 × 1000 mm
  • Maximum permitted static differential pressure for a closed multileaf damper: 2000 Pa
  • Operating temperature: 0 to 60 °C



Sizing data



  • qv  (m³/h)
  • Δpt [Pa]

Air-regenerated noise

  • LPA [dB(A)]


JZ-LL-AL / 1200 × 800 / ER / Z64 / NO / P1 – RAL …
||||||
123456
1 Type
JZ-LL-AL Low-leakage multileaf damper made of aluminium, closed multileaf damper air leakage to EN 1751, class 4
 
2 Nominal size [mm]
B × H
 
3 Installation subframe
No entry required: None
ER With installation subframe
 
4 Attachments
Z04 Hold open device
Z05 – Z07 Quadrant stay and limit switches
Z12 – Z51 Actuators
ZF01 – ZF15 Spring return actuators
Z60 – Z77 Pneumatic actuators
 
5 Damper blade safety function
Only for spring return actuators or pneumatic actuators
NO Pressure off/power off to OPEN
NC Pressure off/power off to CLOSED
 
6 Surface
No entry required: Standard construction
P1 Powder-coated, specify RAL CLASSIC colour
S3 Anodised, E6-C-0, colour according to EURAS standard
 
Gloss level
RAL 9010 50 %
RAL 9006 30 %
All other RAL colours 70 %
 
 
 
Order example: JZ-LL-AL/800×500/Z04/S3
Nominal size800 × 500 mm
Installation subframeNone
AttachmentsHold open device
User interfaceAnodised, EURAS E6-C-0, natural colour

Dimensions, Attachments, Product details, Installation details

  • Dimensions
  • Attachments
  • Product details
  • Installation details

Quadrant stays and limit switches


Order code detailDescriptionLimit switchFunction
Z04Hold open device
Z05Hold open device1Damper blade position CLOSED
Z06Hold open device1Damper blade position OPEN
Z07Hold open device2Damper blade positions CLOSED and OPEN


Open/close actuators

Order code detailDescriptionFunctionSupply voltageTorqueAuxiliary switch
Z12SM230A1-wire-control

2-wire-control (3-point)
100 – 240 V AC20 Nm
Z14SM24A1-wire-control

2-wire-control (3-point)
24 V AC/DC20 Nm
Z16SM230A1-wire-control

2-wire-control (3-point)
100 – 240 V AC20 NmS2A
Z18SM24A1-wire-control

2-wire-control (3-point)
24 V AC/DC20 NmS2A
Z43NM230A1-wire-control

2-wire-control (3-point)
100 – 240 V AC10 Nm
Z45NM24A1-wire-control

2-wire-control (3-point)
24 V AC/DC10 Nm
Z47NM230A1-wire-control

2-wire-control (3-point)
100 – 240 V AC10 NmS2A
Z49NM24A1-wire-control

2-wire-control (3-point)
24 V AC/DC10 NmS2A

Minimum torque of multileaf damper has to be considered when selecting the actuator
accordingly.



Open/close actuators, fast-running

Order code detailDescriptionFunctionSupply voltageTorqueAuxiliary switch
ZS21SMQ24A1-wire-control24 V AC/DC16 Nm
ZS22SMQ24A1-wire-control24 V AC/DC16 NmS2A

Only up to height H ≤ 650 mm



Open/close actuators, spring return

Order code detailDescriptionFunctionSupply voltageTorqueAuxiliary switch
ZF01NF24ASupply voltage on/off24 V AC/DC10 Nm
ZF02NFASupply voltage on/off24 – 240 V AC

24 – 125 V DC
10 Nm
ZF03NF24A-S2Supply voltage on/off24 V AC/DC10 Nmintegrated
ZF04NFA-S2Supply voltage on/off24 – 240 V AC

24 – 125 V DC
10 Nmintegrated
ZF06SF24ASupply voltage on/off24 V AC/DC20 Nm
ZF07SFASupply voltage on/off24 – 240 V AC

24 – 125 V DC
20 Nm
ZF08SF24A-S2Supply voltage on/off24 V AC/DC20 Nmintegrated
ZF09SFA-S2Supply voltage on/off24 – 240 V AC

24 – 125 V DC
20 Nmintegrated
ZF11EF24ASupply voltage on/off24 V AC/DC30 Nm
ZF12EF230ASupply voltage on/off100 – 240 V AC30 Nm
ZF13EF24A-S2Supply voltage on/off24 V AC/DC30 Nmintegrated
ZF14EF230A-S2Supply voltage on/off100 – 240 V AC30 Nmintegrated

Minimum torque of multileaf damper has to be considered when selecting the actuator.



Modulating actuators


Order code detailDescriptionFunctionSupply voltageTorqueAuxiliary switch
Z20SM24A-SR2 – 10 V DC24 V AC/DC20 Nm
Z21GM24A-SR2 – 10 V DC24 V AC/DC40 Nm
Z51NM24A-SR2 – 10 V DC24 V AC/DC10 Nm

Minimum torque of multileaf damper has to be considered when selecting the actuator.



Modulating actuators, spring return


Order code detailDescriptionFunctionSupply voltageTorqueAuxiliary switch
ZF05NF24A-SR2 – 10 V DC24 V AC/DC10 Nm
ZF10SF24A-SR2 – 10 V DC24 V AC/DC20 Nm
ZF15EF24A-SR2 – 10 V DC24 V AC/DC30 Nm

ZF05: Only up to height H ≤ 650


Double acting pneumatic actuators

Order code detailDescriptionDamper blade safety functionOperating pressureTorque at 6 barLimit switchSolenoid valve
Z60DR0301.2 – 6 bar35 Nm
Z61DR030power off to close/open1.2 – 6 bar35 Nm24 V DC
Z62DR030power off to close/open1.2 – 6 bar35 Nm230 V AC
Z63DR0301.2 – 6 bar35 Nm2
Z64DR030power off to close/open1.2 – 6 bar35 Nm224 V DC
Z65DR030power off to close/open1.2 – 6 bar35 Nm2230 V AC
Z66DR0601.2 – 6 bar70 Nm
Z67DR060power off to close/open1.2 – 6 bar70 Nm24 V DC
Z68DR060power off to close/open1.2 – 6 bar70 Nm230 V AC
Z69DR0601.2 – 6 bar70 Nm2
Z70DR060power off to close/open1.2 – 6 bar70 Nm224 V DC
Z71DR060power off to close/open1.2 – 6 bar70 Nm2230 V AC

Minimum torque, which depends on the nominal size of multileaf damper, and the operating pressure have to be considered when selecting the actuator.



Single acting pneumatic actuators


Order code detailDescriptionDamper blade safety functionOperating pressureLimit switchTorque at 6 barSolenoid valve
Z72SC060
SO060
pressure off to close/open6 bar30 Nm
Z73SC060
SO060
power off and pressure off to close/open6 bar30 Nm24 V DC
Z74SC060
SO060
power off and pressure off to close/open6 bar30 Nm230 V AC
Z75SC060
SO060
pressure off to close/open6 bar30 Nm2
Z76SC060
SO060
power off and pressure off to close/open6 bar30 Nm224 V DC
Z77SC060
SO060
power off and pressure off to close/open6 bar30 Nm2230 V AC



Drive shafts (special accessory) upon request

Installation and commissioning

  • With horizontal or vertical blades
  • With or without installation subframe
  • Torsion-free installation
  • Only for installation in internal spaces

Téléchargements

Information produit

Certificats

Manuels d'utilisation

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://api.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://psp40.onventis.com https://psp22.onventis.com https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Partager la page

Recommander cette page

Recommander cette page en envoyant un lien par mail.

Les champs marqués d'un (*) sont obligatoires.

Partager la page

Merci pour votre recommandation !

Votre recommandation a été envoyée et devrait arriver dans les plus brefs délais.

Contact

Nous sommes à votre disposition

Veuillez préciser votre message et le type de demande
Tel.: +32 (0) 2/522 07 80

Les champs marqués d'un (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +32 (0) 2/522 07 80

Contact

Nous sommes à votre disposition

Veuillez préciser votre message et le type de demande
Tel.: +32 (0) 2/522 07 80

Pièce jointe (max. 10MB)

Les champs marqués d'un (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +32 (0) 2/522 07 80