FSL-V-ZAB/SEK 

Supply and extract air unit with heat exchanger and heat recovery unit, secondary air option, for vertical installation on an external wall, e.g. adjacent to a window

Ready-to-operate decentralised ventilation unit that provides good comfort levels, used for the ventilation of rooms

  • Acoustically optimised EC fans with low specific fan powers, SFP-1 according to EN 13779
  • Recuperative plate heat exchanger (air/air), including bypass damper with electric actuator (open-close)
  • Heat exchanger for heating and cooling as 2-pipe or 4-pipe system
  • Unit base of approx. 0.13 m²
  • Reduction of fine dust and pollen contamination due to integral filters that conform to VDI 6022 – F7 fresh air filter and G3 extract air filter
  • Condensate drip tray with condensate drain
  • Motorised shut-off damper, normally closed (NC)
  • Automatic switching to secondary air mode (based on air quality)


Optional equipment and accessories

  • Modular control system FSL-CONTROL II, specially for decentralised ventilation systems
  • Demand-based fresh air volume, free cooling and night purge, depending on control strategy
  • Variable heat recovery
  • Powder-coated RAL 9005

Application

Application

  • Ventilation of rooms, preferably rooms with a depth up to 6 m
  • 2-pipe or 4-pipe heat exchangers enable good comfort levels
  • Inducing displacement flow
  • Energy-efficient solution since water is used for heating and cooling
  • For new buildings, refurbishment projects and revitalisation projects
  • Vertical installation on the façade or on an external wall
  • Typical installation locations include offices and meeting rooms

Special characteristics

  • Motorised shut-off dampers for fresh, normally closed (NC) in order to prevent uncontrolled airflows
  • Recuperative heat recovery unit, including bypass damper with electric variable actuator
  • Heat exchanger as 2-pipe or 4-pipe system, with G½" union nuts and flat seals
  • Meets the hygiene requirements of VDI 6022
  • Filter class: F7 for fresh air, G3 for extract air
  • Easy filter change with quick release fasteners, no tools required
  • Condensate drip tray with or without condensate drain
  • Compact construction, hence particularly suitable for refurbishment projects
  • Demand-based ventilation and extract ventilation is possible by means of monitoring the room air quality and with dedicated control equipment
  • 4 levelling feet
  • Automatic switching to secondary air mode (only with an air quality sensor) if the room air quality (measured with the integral VOC sensor, for example) is between the previously defined range. The fresh air damper closes, the self-powered secondary air damper opens and the extract air fan is switched off. The unit always starts in secondary air mode, which is more energy efficient.

Nominal sizes

  • 396 × 1800 × 319 mm (B × H × T)

Technical information

Function, Technical data, Quick sizing, Specification text, Order code, Related products

  • Function
  • Technical data
  • Quick sizing
  • Specification text
  • Order code

Functional description

Decentralised supply and extract air units for room ventilation and for dissipating cooling loads and heat loads.

An EC centrifugal fan takes in the fresh air which then flows through the motorised shut-off damper and the F7 filter.

Once the fresh air has passed the fan, it flows through the heat recovery unit; it is possible to bypass the heat exchanger in order to protect it, or when it is sensible with regard to energy efficiency.

If necessary, the air is heated or cooled by the heat exchanger before it is discharged to the room as a displacement flow.

The extract air first passes a G3 filter (that protects the unit), then flows through the heat recovery unit, the extract air fan and the motorised shut-off damper before it is discharged to the outside as exhaust air.

Automatic switching to secondary air mode (only with an air quality sensor) if the room air quality is sufficient.

The fresh air damper closes, the self-powered secondary air damper opens and the extract air fan is switched off.

The unit always starts in secondary air mode, which is more energy efficient.

Width

396 mm

Height

1800 mm

Depth

319 mm

Fresh air flow rate

150 m³/h

Supply air flow rate

Up to 150 m³/h

Cooling capacity

Up to 720 W

Heating capacity

Up to 2650 W

Room cooling capacity

Up to 400 W

Room heating capacity

Up to 750 W

Max. operating pressure, water side

6 bar

Max. operating temperature

75 °C

Sound power level

27 – 44 dB(A)

Supply voltage

230 V AC ±10 %, 50/60 Hz


FSL-V-ZAB/SEK (sizing examples)

Supply air flow rate

m³/h

60

90

120

150

Total cooling capacity

W

287

409

563

688

Room cooling capacity

W

174

240

337

406

Air temperature inside the unit

°C

32.0

32.0

32.0

32.0

Rel. humidity

%

40.0

40.0

40.0

40.0

Water content of the dry air

g/kg

11.9

11.9

11.9

0.0

Supply air temperature

°C

17.3

18.0

17.6

17.9

Condensation

g/h

0

0

0

0

Chilled water flow rate

l/h

30

40

80

100

Water temperature, inlet

°C

16

16

16

16

Water temperature, outlet

°C

24.2

24.8

22.0

21.9

Water side pressure drop

kPa

1.5

2.4

8.5

12.7

Total heating capacity

W

1070

1620

2050

2460

Room heating capacity

W

269

412

449

471

Air temperature inside the unit

°C

–12.0

–12.0

–12.0

–12.0

Supply air temperature

°C

35.4

35.7

33.2

31.4

Hot water flow rate

l/h

30

60

80

100

Water temperature, inlet

°C

50

50

50

50

Water temperature, outlet

°C

19.1

26.6

27.8

28.7

Sound power level LWA

dB(A)

27

33

39

44

Sound pressure level with 8 dB system attenuation

dB(A)

19

25

31

36


Decentralised supply and extract air units of Type FSL-V-ZAB/SEK, with heat recovery and heat exchanger, for vertical installation on the façade system or on an external wall, e.g. adjacent to a window.

Special characteristics

  • Motorised shut-off dampers for fresh, normally closed (NC) in order to prevent uncontrolled airflows
  • Recuperative heat recovery unit, including bypass damper with electric variable actuator
  • Heat exchanger as 2-pipe or 4-pipe system, with G½" union nuts and flat seals
  • Meets the hygiene requirements of VDI 6022
  • Filter class: F7 for fresh air, G3 for extract air
  • Easy filter change with quick release fasteners, no tools required
  • Condensate drip tray with or without condensate drain
  • Compact construction, hence particularly suitable for refurbishment projects
  • Demand-based ventilation and extract ventilation is possible by means of monitoring the room air quality and with dedicated control equipment
  • 4 levelling feet
  • Automatic switching to secondary air mode (only with an air quality sensor) if the room air quality (measured with the integral VOC sensor, for example) is between the previously defined range. The fresh air damper closes, the self-powered secondary air damper opens and the extract air fan is switched off. The unit always starts in secondary air mode, which is more energy efficient.

Materials and surfaces

  • Casing, filter chamber cover, fans and levelling feet are made of galvanised sheet steel
  • Heat exchanger with copper tubes and aluminium fins
  • Casing powder-coated, black (RAL 9005)
  • F7 filter medium made of moisture-resistant glass fibre paper (certified by Eurovent)
  • Mineral wool lining to DIN 4102, fire rating class A, faced with glass fibre fabric as a protection against abrasion, effective with airflow velocities up to 20 m/s
  • Closed cell sealing strips

Construction

  • Powder-coated RAL 9005, black

Technical data

  • Width: 396 mm
  • Height: 1800 mm
  • Depth: 319 mm
  • Fresh air flow rate: 150 m³/h
  • Supply air flow rate: up to 150 m³/h
  • Cooling capacity: up to 720 W
  • Heating capacity: up to 2650 W
  • Room cooling capacity: up to 400 W
  • Room heating capacity: up to 750 W
  • Max. operating pressure: 6 bar
  • Max. operating temperature: 75 °C
  • Sound power level: 27 – 44 dB(A)
  • Supply voltage: 230 V AC ±10 %, 50/60 Hz
  • Rating: 87 VA
  • Power consumption: nominal volume flow rate 27 W

Sizing data

Fresh air

  • V_________________[m³/h]

Supply air

  • V_________________[m³/h]

Room cooling capacity

  • Q_________________[W]

Room heating capacity

  • Q_________________[W]


  • LWA_______________[dB(A)]

00255822_0

 Type
FSL-V-ZAB/SEK       Vertical ventilation units

 Heat exchanger
2       2-pipe
4       4-pipe

 Dimensions [mm]
       B × H × T
396 × 1800 × 319

 Control
       No entry: none
R       With

 Control function
MA       Master (room module and control module)
SL       Slave (control module)

 Real time clock
       No entry: none
       master only
T       With

 Interface
       No entry: none
       master only
B       BACnet MS/TP or Modbus RTU
L       LonWorks LON-FTT10

 Air quality sensor
       No entry: none
       master only
V       VOC sensor

 

 Supply air temperature sensor
Z       With

 Fresh air temperature sensor
       No entry: none
       master only
A       With

 Heating valve
HV       With

 Lockshield – heating circuit
R       With

 kVS value – heating valve
0,25
0,40
0,63
1,00
F0,50

 Cooling valve
       For 4-pipe systems only
KV       with

 Lockshield – cooling circuit
R       With

 kVS valve – cooling valve
0,25
0,40
0,63
1,00
F0,50

Decentralised ventilation units are technically advanced products of high quality; they offer a wide range of configuration options. For specification details regarding your project please contact your nearest TROX branch or subsidiary.

 

Dimensions and weight

  • Dimensions and weight
FSL-V-ZAB/SEK 00260148_0


Installation examples, Installation details, Basic information and nomenclature

  • Installation examples
  • Installation details
  • Basic information and nomenclature

Installation and commissioning

  • Vertical installation on the façade or on an external wall
  • Level adjustment using the 4 levelling feet (+40 mm)
  • The fresh air connection is provided by two ventilation openings in the façade system or external wall (to be provided by others), preferably sloping towards the outside
  • Weather protection for the fresh air and exhaust air openings to be provided by others
  • Installation and connections to be performed by others; fixing, connection and sealing material to be provided by others
  • The water flow and return connections are on the right-hand side of the unit when seen from the room
  • Vents and drainage by others
  • The electrical connection is on the right when seen from the room
  • The under sill trim must not obstruct installation or deinstallation of the unit or maintenance access on the front of the unit

Nomenclature

LWA [dB(A)]

Sound power level

tPr [°C]

Primary air temperature

tWV [C°]

Water flow temperature – cooling/heating

tR [C°]

Room temperature

tAN [C°]

Secondary air intake temperature

QPr [W]

Thermal output – primary air

Qtot [W]

Thermal output – total

QW [W]

Thermal output – water side, cooling/heating

VPr [l/s/m³/h]

Primary air volume flow rate

VW [l/h]

Water flow rate – cooling/heating

V [l/h]

Volume flow rate

∆tW [K]

Temperature difference – water

∆pW [kPa]

Water side pressure drop

∆pt [Pa]

Total pressure drop, air side

∆tPr = tPr - tR [K]

Difference between primary air temperature and room temperature

∆tRWV = tWV - tR [K]

Difference between water flow temperature and room temperature

∆tWm-Ref [K]

Difference between mean water temperature and reference temperature

Principal dimensions

LN [mm]

Nominal length

Inducing displacement flow

The supply air is discharged near the external wall and with a medium velocity between 1.0 and 1.5 m/s. Due to the induction effect the supply air velocity is rapidly reduced such that, in cooling mode, the supply air displaces the room air over the entire floor area. The convection from people and other heat sources causes the fresh air from the pool to rise and create comfortable conditions in the occupied zone.

Heat exchanger

The maximum water-side operating pressure for all heat exchangers is 6 bar.

The maximum water flow temperature (heating circuit) for all heat exchangers is 75 °C; if flexible hoses are used, the water flow temperature should not exceed 55 °C. Units for other pressures and temperatures are available on request.

The water flow temperature (cooling circuit) should be at least 16 °C such that it does not permanently fall below the dew point. For units with a condensate drip tray the water flow temperature may be reduced to 15 °C.

Heat exchanger as 2-pipe system

Air-water systems with a 2-pipe heat exchanger may be used for either heating or cooling. In changeover mode it is possible to use all units within a water circuit exclusively for cooling in summer and exclusively for heating in winter.

Heat exchanger as 4-pipe system

Air-water systems with a 4-pipe heat exchanger may be used for both heating and cooling. Depending on the season, i.e. especially in spring and autumn, it may be possible that an office has to be heated in the morning and cooled in the afternoon.

Downloads

product information

certificates

operation manuals

References

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://*.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://*.onventis.com http://localhost:63342 http://cerebrum.local", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be